Decision Lab · D6 · Sensor evidence, priorities and reset permission
A safety latch changes what the controller may do
Read the stated sequence as a set of permissions. A normal temperature error does not authorize bypassing an active protective state.
By the end of this workshop
- Choose a method that respects the supplied conditions.
- Explain how a changed condition affects the decision.
- Identify a physical or procedural cross-check and an applicability limit.
- Record the assumption you would verify next time.
Start with the complete model
Givens and assumptions
- Original training sequence: normal cooling modulates when room temperature exceeds 75°F.
- A coil temperature at or below 35°F, or a coil-sensor fault, latches the protective state.
- Latched state commands supply fan OFF, outdoor-air damper CLOSED, heating valve 100% and cooling valve 0%.
- Release requires a healthy coil sensor, coil temperature above 42°F and an operator reset. All three conditions are required.
- Current room temperature 82°F; coil temperature 34°F; sensor healthy. The protective state is active.
Study calculator, scratch notepad and whiteboard
Sketch a control volume or air path with a mouse, pen or touch. Ink stays in this page session and clears on reload. Use the response and reflection fields as a keyboard alternative. Sign in before starting and save a reflection to retain your reasoning.
1 · Choose the method
Which command set follows the supplied active protective state at room 82°F and coil 34°F?
2 · Change the condition
Predict before you inspect the calculation.
The coil reaches 45°F with a healthy sensor, but no operator reset has occurred.
- The same original latch-release rule requires a healthy coil sensor, coil above 42°F and an operator reset. Coil is now 45°F, sensor healthy, reset absent; room remains 82°F.
Check the first decision to open the changed-condition response.
Reference navigation drill
Search concept: controls, sensors, actuators, integral action
Explain the distinction between setpoint reset, integral reset and manual latch release.
Where this model stops
Original illustrative sequence only. Real protective actions and reset requirements depend on the approved design and equipment instructions. Do not adopt this command set as a general design rule.
The PE Mechanical: HVAC and Refrigeration examination uses the NCEES PE Mechanical Reference Handbook. These source links provide study context; they are not additional exam-day references.
Found an unclear condition or calculation? Include workshop latched-control-sequence and the step in your comment.